本文研发了基于环境信息和导线温度的动态增容监控系统,在不突破现有技术规程的条件下提高输电线路的输送容量。文中首次提出采用主副分机、双无线通信(无线电和GSM SMS)的工作模型进行导线温度和环境温度、风速、日照强度等信息的采集,采用摩尔公式计算当前线路的隐性载流量,并给出了现场监测主副分机的软硬件设计、数字温度传感器DS18B20的程序设计以及专家软件设计等。关键词:动态增容,主副分机,隐性载流量,DS18B20Abstract: An on-line monitoring system of dynamic capacity-increase of transmission lines has been developed, by which the capacity of transmission lines can be increased in the precondition that the present specifications of conductors remain unchanged. The master and slave monitoring units were firstly adopted to measure the conductor temperature, the ambient temperature, the wind speed, and the solar radiation intensity by wireless communication, and these data were sent to the municipal monitoring and controlling center by GSM SMS. The latent capacity was calculated by mole formula. The hardware design and software design of the master and slave monitoring units, the program of digital temperature sensor named DS18B20, and the design of expert software were introduced in this paper.key words: Dynamic capacity increasing; Master and slave units, Latent capacity; DS18B20